Panasonic Electric Works Nordic ABMEW01351 Rev: - Planning Instructions Fire alarm system EBL512 G3, V1.1.x7613.5 Control expressionEach programmable output has to be given a control expression. It iscreated by so called Boolean algebra.Trigger conditions (see "Available functions"), logical "Operators"(AND, OR, NOT) and parentheses are used to make a "controlexpression" containing up to 40 trigger conditions. See also chapter"Control expression examples" page 80 and WinG3 help.A programmable output will be activated as long as its controlexpression is true.Figure 15. In any output dialog box, click the right mousebutton in the large white field to show a "Trigger conditions list".Depending on the selected trigger condition, differentarguments / data have to be entered.13.5.1 Trigger conditionsSome trigger conditions require additional information, seeinformation within parentheses (+nnnnn) after the trigger conditionrespectively below.The following trigger conditions are available (numbering only for thecomments below):1 Fire Alarm Zone (+Zone no.)2 Fire Alarm Zone Address (+Zone no.+Address)3 General Fire Alarm4 Consecutive Fire Alarm (sequence) (+start Zone no. andaddress +stop Zone no. and address +Quantity)5 Pre Warning Zone (+Zone no.)6 Pre Warning Zone Address (+Zone no.+Address)7 General Pre Warning8 Consecutive Pre Warning (+start Zone no. and address+stop Zone no. and address +Quantity)