Panasonic Electric Works Nordic ABMEW01351 Rev: - Planning Instructions Fire alarm system EBL512 G3, V1.1.x107If a fire alarm type A is received, the probability of a real fire is higherthan for a fire alarm type B. The alarm receiver can take differentactions depending on if it is a type A or B fire alarm.16.15.1 Fire alarm type BThe output shall be programmed (via WinG3) as type "Routingequipment" and have the trigger condition "One detector alarm".The output will be activated for fire alarm from one analogaddressable smoke, heat or multi101 detector only.16.15.2 Fire alarm type AThe output shall be programmed (via WinG3) as type "Routingequipment" and have the trigger condition "Multiple detectoralarm".The output will be activated for fire alarm from: Two or more analog addressable smoke, heat or multidetectors. Any manual call point Any zone line input Any programmable input with the trigger condition "GeneralFire"16.16 Disable alarm points and outputsTemporary disablements are made via the menu H2 sub menus. Formore information see EBL512 G3 Operating Instructions MEW01163,chapter "Disable or re-enable (H2)". The disablements are re-enabledvia the menu H2 sub menus.Regular disablements are made via time channels, see chapter "Timechannels", page 134.When alarm reset method "Single with automatic disablement" isselected via the WinG3 "System Properties", the function will be asfollows:If an alarm point or zone is in alarm state when being reset it will notonly be reset but also disabled. It has to be re-enabled (via menuH2/B5) the same way as if it was disabled via menu H2/B1-B2.Disabled alarm points and outputs are indicated by LED Fault /Disablements "General disablements" on the c.i.e. front and are listedin menu H4/U1-U2.Enhanced Disablement (Default) = Fire alarm, pre-warning and faultsignal cannot be activated by the disabled alarm point/zone. If onlyfire alarm and pre-warning shall be disabled, "Enhanced Disablement"101 NOTE! A multi detector can have one presentation number (Zone-Address) or two presentation numbers depending on how it is programmedvia WinG3. One presentation number = one detector and two presentationnumbers = two detectors regarding fire alarm types A and B.