Panasonic Electric Works Nordic ABMEW01351 Rev: - Planning Instructions Fire alarm system EBL512 G3, V1.1.x143 Overview3.1 The EBL512 G3 systemEBL512 G3 is a microprocessor controlled intelligent fire alarmsystem, intended for analog addressable smoke detectors, as well asconventional detectors and manual call points. Programmable controloutputs and output units are available. Up to 1020 addresses (ofwhich up to 512 can be alarm points) can be connected to each controlunit (c.i.e.) - according to EN54-2.EBL512 G3 is available in several types, versions and configurations.It can be connected to a TLON network, i.e. in a "system" with up to30 control units. Each control unit has access to all information.Product type no. Product name5000 EBL512 G3 c.i.e. With or without a printer.With front and display.5001 EBL512 G3 c.i.e.Without front, display and printer. No door.EBL512 G3 is designed according to the European standard EN54,part 2 and 4. The Swedish front conforms to SS3654.3.1.1 PrinterThe control unit EBL512 G3 type 5000 can be delivered with a printer("PRN" included in the article number) or without a printer.3In Ext. Fire Brigade Panel 1826 it is possible to mount an optionalPrinter 1535.3.1.2 Expansion boardsIn the control unit (c.i.e.) it is possible to mount up to six expansionboards. The following types are available:Product type no. Product name Note4580 8 zones expansion board4581 8 relay outputs expansion board4583 In- and outputs expansion boardRegarding the expansion boards, see also chapter "Expansion boards458x, page 26 and EBL512 G3 drawings.3.1.3 Power supplyThe main power source is a built-in switched power supply (rectifier)5037. 230 V AC, 1.6 A / 24 V DC, 6.5 A.The second power source is a backup battery (2 x 12 V). In the c.i.e.3 Printer 5058 is a spare part for the c.i.e. type 5000 with a printer, i.e. itcomes without a mounting frame etc.