Panasonic Electric Works Nordic ABMEW01351 Rev: - Planning Instructions Fire alarm system EBL512 G3, V1.1.x11416.28.1 Daylight saving timeThe time is automatically changed when the Daylight saving timeperiod starts and stops respectively, if set so in WinG3. When, isdepending on which convention that is used: Australian convention: Forward 1 hour the first Sunday inOctober, 02:00 03:00. Backward 1 hour the first Sunday inApril, 03:00 02:00. New Zealand convention: Forward 1 hour the last Sunday inSeptember, 02:00 03:00. Backward 1 hour the first Sundayin April, 03:00 02:00. All other conventions: Forward 1 hour the last Sunday inMarch, 02:00 03:00. Backward 1 hour the last Sunday inOctober, 03:00 02:00.16.29 Loss of main power sourceRegarding the Main power source and Second power source, seechapter "Power supply", page 152.16.29.1 Fault: Loss of main power sourceThe delay time for the fault "Loss of main power source" can be set(in WinG3) to 1 – 300 minutes. (A delay time > 30 minutes is aviolation to the EN54-2 standard.16.29.2 LCD backlightIn order to reduce the current consumption the LCD backlight willnever be turned on during loss of the main power source.Exceptions Australian convention: The LCD backlight will be turned onalso during loss of the main power source. New Zealand convention: The LCD backlight will be turned onalso during loss of the main power source.16.30 EvacuateWhen the soft key "Evacuate" (P7)112 is pressed113, all outputsprogrammed for sounders (i.e. type "Alarm devices"), will becollective turned ON (steady). This is indicated in the LCD:Evacuate in progress112 The soft key "Evacuate" is only visible / valid for the Belgian, BritishStandard, Hungarian, Spanish and Ukrainian conventions.113 Alt. when a programmable input is activated. One input per c.i.e.