Panasonic Electric Works Nordic ABMEW01351 Rev: - Planning Instructions Fire alarm system EBL512 G3, V1.1.x39NOTE! The COM loop address for the Addressable Base station forwireless units (4610) is set on a DIL-switch in the unit respectively.The COM loop address for a wireless detector (4601) is depending onwhich Base station it is "connected" to, see chapter "Other COM loopunits", page 51.9.1.1 Input unitsEach COM loop input unit is added and programmed via WinG3.Depending on type of unit, regarding: Technical address (COM loop address) 001-255 Name (normally not changed) Zone number and Address within the zone Alarm text (user definable) Regular Alarm algorithm (some units only) Options: Alternative Alarm algorithm & Time Channel (some units only) Alert annunciation & Time Channel (some units only) Disablement & Time Channel (some units only) Two-units-dependent fire alarm, i.e. co-incidence alarm & TimeChannel (some units only) Delayed (fire alarm) Quiet alarm (Australian function)Figure 7. An example of a WinG3 dialog box is the "Analogphoto electric smoke detector 4301" dialog box.For more information, see WinG3 help.Connections, if nothing else is specified, see drawing 512 G3 - 31.