Panasonic Electric Works Nordic ABMEW01351 Rev: - Planning Instructions Fire alarm system EBL512 G3, V1.1.x12819 Control unit propertiesFigure 25. The WinG3 "Control unit properties" dialog box.NOTE! Default settings in WinG3 might vary depending onconvention.19.1 Control unit properties dialog boxOpens when you add a control unit or via the "Control unit" pop-upmenu (Properties...)19.1.1 General InformationNumber: A stand-alone control unit has to have no. 0. In a system(TLON Network) the control units are numbered from 0 to 29.Name: Normally not changed but can be changed when required.19.1.2 Peripherals MMI board (default): This check box shall be marked when thec.i.e. has a front with display (i.e. EBL512 G3 type 5000).This check box shall not be marked when the c.i.e. has no front(i.e. EBL512 G3 type 5001). Printer (only valid for EBL512 G3 type 5000) This check boxshall be marked when the c.i.e. is equipped with a printer.19.1.3 Misc.Configured number of alarm points: 128, 256 or 512.NOTE! 1020 COM loop unit addresses are always available but max.512 of these 1020 addresses can be alarm points.In the Australian convention only, the number of alarm points perc.i.e. can be set to 128, 256, 512 or 1020.