n Setup Group ParametersTable 4.6 lists the parameters available by default in the Setup Group. Selecting an Application Preset in through initializationin parameter A1-03 automatically changes the parameters selected for the Setup Group. Refer to Fan and Pump ApplicationPresets on page 125 for details on parameters and default values for the fan and pump Setup Groups.No. Parameter Name Setting Range DefaultA1-03 Initialize Parameters 0, 1110, 2220, 3330, 5550,8008, 8009, 8010, 8011 0Setting 0: No initialization (default)Setting 1110: User Initialize (parameter values must be stored using parameter o2-03)Setting 2220: 2-Wire InitializeSetting 3330: 3-Wire InitializeSetting 5550: Terminal/Control InitializeSetting 8008: PumpSetting 8009: Pump w/ PISetting 8010: FanSetting 8011: Fan w/ PIUse the Programming Mode to access parameters not displayed in the Setup Group.Table 4.6 General Purpose Application Setup Group Parameters (A1-03 = 0)Parameter NameA1-06 Application Preset Selection (Monitor only)b1-01 Frequency Reference Selection 1b1-02 Run Command Selection 1b1-03 Stopping Method Selectionb1-04 Reverse Operation SelectionC1-01 Acceleration Time 1C1-02 Deceleration Time 1d1-01 Frequency Reference 1d2-01 Frequency Reference Upper Limitd2-02 Frequency Reference Lower LimitParameter NameE2-01 Motor Rated CurrentL2-01 Momentary Power Loss Operation SelectionL5-01 Number of Auto Restart AttemptsL6-01 Torque Detection 1 SelectionL6-02 Torque Detection 1 LevelL6-03 Torque Detection 1 Timeo1-06 User Monitor Selection Modeo1-07 Second Line Monitor Selectiono1-08 Third Line Monitor Selectionu Switching Between LOCAL and REMOTELOCAL mode is when the drive is set to accept the Run command from the digital operator RUN key. REMOTE mode iswhen the drive is set to accept the Run command from an external device (i.e., input terminals or serial communications).WARNING!Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching fromLOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery.Switch the operation between LOCAL and REMOTE using the LO/RE key on the digital operator or via a digital input.Note: 1. After selecting LOCAL, the LO/RE light will remain lit.2. The drive will not allow the user to switch between LOCAL and REMOTE during run.4.2 The Drive, Programming, and Clock Adjustment Modes86 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide