A.1 Power Ratingsu Three-Phase 200 V Class Drive Models 2A0004 to 2A0030Table A.1 Power Ratings (Three-Phase 200 V Class)Item SpecificationDrive Model 2A0004 2A0006 2A0008 2A0010 2A0012 2A0018 2A0021 2A0030Maximum ApplicableMotor Capacity (HP) <1> ND Rating 0.75 1 2 3 3 5 7.5 10InputInput Current (A) <2> ND Rating 3.9 7.3 8.8 10.8 13.9 18.5 24 37Rated VoltageRated Frequency Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc <3>Allowable Voltage Fluctuation -15 to 10%Allowable Frequency Fluctuation ±5%Input Power (kVA) ND Rating 2.2 3.1 4.1 5.8 7.8 9.5 14 18OutputRated Output Capacity(kVA) <4> ND Rating <5> 1.3 2.3 3 3.7 4.6 6.7 8 11.4Rated Output Current (A) ND Rating <5> 3.5 6 8 9.6 12 17.5 21 30Overload Tolerance ND Rating: 120% of rated output current for 60 s(Derating may be required for applications that start and stop frequently)Carrier Frequency User-adjustable between 1 and 15 kHz <5>Maximum Output Voltage (V) Three-phase 200 to 240 V (proportional to input voltage)Maximum Output Frequency (Hz) 400 Hz (user-set)<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater thanthe motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiringconnections, and power supply impedance.<3> DC is not available for UL/CE standards.<4> Rated motor capacity is calculated with a rated output voltage of 220 V.<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settingsraise the carrier frequency and require current derating.A.1 Power Ratings170 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide