B.9 o: Operator-Related SettingsThe o parameters set up the digital operator displays.u o1: Digital Operator Display SelectionNo.(Addr.Hex) Name Description Values Pageo1-01(500) Drive Mode Unit MonitorSelectionSelects the content of the last monitor that is shown when scrolling throughDrive Mode display. Enter the last three digits of the monitor parameternumber to be displayed: Uo-oo.Default: 106(Monitor U1-06)Range: 104 to 809 –o1-02(501) User Monitor Selection afterPower Up1: Frequency reference (U1-01)2: Direction3: Output frequency (U1-02)4: Output current (U1-03)5: User-selected monitor (set by o1-01)Default: 1Range: 1 to 5 –o1-03(502) Digital Operator DisplaySelectionSets the units the drive should use to display the frequency reference and motorspeed monitors.0: 0.01 Hz1: 0.01% (100% = E1-04)2: r/min (calculated using the number of motor poles setting in E2-04)3: User-selected units (set by o1-09, o1-10 and o1-11)Default: 0Range: 0 to 3 –o1-06(517) User Monitor SelectionModeSelects the monitors displayed on the second and third lines of the digitaloperator display.0: 3 Monitor Sequential (displays the next two sequential monitors)1: 3 Monitor Selectable (set by o1-07 and o1-08)Default: 0Range: 0, 1 –o1-07(518) Second Line MonitorSelectionSelects the monitor that is shown in the second line.Enter the last three digits of the monitor parameter number to be displayed:Uo-oo. For example, set "403" to display monitor parameter U4-03.Note: Parameter is effective only when o1-06 is set to 1.Default: 102Range: 101 to 799 –o1-08(519) Third Line MonitorSelectionSelects the monitor that is shown in the third line.Enter the last three digits of the monitor parameter number to be displayed:Uo-oo. For example, set "403" to display monitor parameter U4-03.Note: Parameter is effective only when o1-06 is set to 1.Default: 103Range: 101 to 799 –o1-09(51C) Frequency ReferenceDisplay UnitsSets unit display for the frequency reference parameters and frequency relatedmonitors when o1-03 = 3.0: WC (Inch of water)1: PSI (Pounds per square inch)2: GPM (Gallons per minute)3: F (Degrees Fahrenheit)4: CFM (Cubic feet per minute)5: CMH (Cubic meters per hour)6: LPH (Liters per hour)7: LPS (Liters per second)8: Bar (Bar)9: Pa (Pascal)10: C (Degrees Celsius)11: Mtr (Meters)12: Ft (Feet)13: LPM (Liters per minute)14: CMM (Cubic meters per minute)15: “Hg (inches of mercury)24: Custom units (determined by o1-13 to o1-15)25: NoneDefault: 25Range: 0 to 15; 24,25 –o1-10(520) User-Set Display UnitsMaximum ValueThese settings define the display values when o1-03 is set to 3.o1-10 sets the display value that is equal to the maximum output frequency.o1-11 sets the position of the decimal position.Default: <1>Range: 1 to 60000 –o1-11(521) User-Set Display UnitsDecimal Display Default: <1>Range: 0 to 3 –o1-13(3105)Frequency Reference andFrequency Related MonitorCustom Units 1Sets the first character of the customer-specified unit display when o1-03 isset to 3 and o1-09 is set to 24. Default: 41Range: 30 to 7A –o1-14(3106)Frequency Reference andFrequency Related MonitorCustom Units 2Sets the second character of the customer-specified unit display when o1-03is set to 3 and o1-09 is set to 24. Default: 41Range: 30 to 7A –B.9 o: Operator-Related Settings218 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide