B.2 b: ApplicationApplication parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PIDcontrol, the Dwell function, Energy Savings, and a variety of other application-related settings.u b1: Operation Mode SelectionNo.(Addr.Hex) Name Description Values Pageb1-01(180) Frequency ReferenceSelection 10: Digital operator1: Analog input terminals2: MEMOBUS/Modbus communications3: Option PCB4: Pulse input (terminal RP)Default: 1Range: 0 to 4 92b1-02(181) Run CommandSelection 10: Digital operator1: Digital input terminals2: MEMOBUS/Modbus communications3: Option PCBDefault: 1Range: 0 to 3 93b1-03(182) Stopping Method Selection0: Ramp to stop1: Coast to stop2: DC Injection Braking to stop3: Coast with timerDefault: 0Range: 0 to 3 94b1-04(183) Reverse Operation Selection 0: Reverse enabled.1: Reverse disabled. Default: 0Range: 0, 1 –b1-07(186) LOCAL/REMOTE RunSelection0: An external Run command must be cycled at the new source in order to beactivated.1: An external Run command at the new source is accepted immediately.Default: 0Range: 0, 1 –b1-08(187) Run Command Selection inProgramming Mode0: Run command is not accepted while in Programming Mode.1: Run command is accepted while in Programming Mode.2: Prohibit entering Programming Mode during run.Default: 0Range: 0 to 2 –b1-11(1DF) Run Delay Time Setting After a Run command is entered, the drive output waits until this delay timehas passed before starting.Default: 0 sMin.: 0Max.: 600 –b1-14(1C3) Phase Order Selection 0: Standard1: Switch phase order (reverses the direction of the motor) Default: 0Range: 0, 1 –b1-15(1C4) Frequency ReferenceSelection 2Enabled when an input terminal set for “External reference” (H1-oo = 2)closes.0: Digital operator1: Terminals (analog input terminals)2: MEMOBUS/Modbus communications3: Option card4: Pulse train inputDefault: 0Range: 0 to 4 –b1-16(1C5) Run CommandSelection 2Enabled when a terminal set for “External reference” (H1-oo = 2) closes.0: Digital operator1: Digital input terminals2: MEMOBUS/Modbus communications3: Option cardDefault: 0Range: 0 to 3 –b1-17(1C6) Run Command at Power Up 0: Disregarded. A new Run command must be issued after power up.1: Allowed. Motor will start immediately after power up if a Run commandis already enabled.Default: 0Range: 0, 1 –u b2: DC Injection Braking and Short Circuit BrakingNo.(Addr.Hex) Name Description Values Pageb2-01(189) DC Injection Braking StartFrequencySets the frequency at which DC Injection Braking starts when “Ramp to stop”(b1-03 = 0) is selected. Default: 0.5 HzMin.: 0.0Max.: 10.0 96b2-02(18A) DC Injection BrakingCurrentSets the DC Injection Braking current as a percentage of the drive rated current. Default: 50%Min.: 0Max.: 100 –b2-03(18B) DC Injection Braking Timeat StartSets DC Injection Braking time at start. Disabled when set to 0.00 seconds. Default: 0.00 sMin.: 0.00Max.: 10.00 –B.2 b: ApplicationYASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide 185B Parameter List