u Three-Phase 600 V Class Drive Models 5A0003 to 5A0032Table A.7 Power Ratings (Three-Phase 600 V Class)Item SpecificationDrive Models 5A0003 5A0004 5A0006 5A0009 5A0011 5A0017 5A0022 5A0027 5A0032Maximum ApplicableMotor Capacity (HP) <1> ND Rating 2 3 5 7.5 10 15 20 25 30InputInput Current (A)<2> ND Rating 3.6 5.1 8.3 12 16 23 31 38 45Rated VoltageRated Frequency Three-phase 500 to 600 Vac 50/60 HzAllowable Voltage Fluctuation -10 (-15) to +10%Allowable FrequencyFluctuation ±5%Input Power(kVA) ND Rating 4.1 5.8 9.5 14 18 26 35 43 51OutputRated OutputCapacity (kVA)<3>ND Rating<4> 2.7 3.9 6.1 9 11 17 22 27 32Rated OutputCurrent (A) ND Rating<4> 2.7 3.9 6.1 9 11 17 22 27 32Overload Tolerance ND Rating: 120% of rated output current for 60 s(Derating may be required for applications that start and stop frequently)Carrier Frequency User-adjustable between 1 and 15 kHz <4> User-adjustable between 1 and 10 kHz <4>Maximum Output Voltage (V) Three-phase 500 to 600 V (proportional to input voltage)Maximum OutputFrequency (Hz) 400 Hz (user-set)<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater thanthe motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiringconnections, and power supply impedance.<3> Rated motor capacity is calculated with a rated output voltage of 575 V.<4> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settingsraise the carrier frequency and require current derating.A.1 Power Ratings176 YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide