GE Grid Solutions D25User's ManualGE Information 994-0081-3.00-21 85Testing Hardware I/O PointsTestingHardware I/OPointsTo test I/O points:• Login to WESMAINT• Navigate to the specific WESMAINT display for the type of points you want totest• Follow the instructions given below for testing specific types of points!Data PointsThe Plant I/O software application version in the D25’s firmware determinesthe quantity and relative position of data points in the System Point DatabaseThe actual point number that you want to test can be determined by:• Viewing the point descriptions that are displayed in WESMAINT• Referring to the SGConfig configuration tables for this specific D25.Note: Actual point descriptions displayed in WESMAINT depend onchanges made to the point descriptions in the running configurationfile.Procedure:Login toWESMAINTWhen the POST is complete, login to WESMAINT to test I/O points.Step Action1 Press ENTER on the PC keyboardResults: The Welcome screen appears, including a Login prompt.Note: If the Welcome banner does not appear, and only a prompt is displayed, a valid code and/orconfiguration file is not loaded into the D25’s memory.Stop this procedure and review procedures for restoringfiles: see D25 Software.2 Type the User Name: westronic and Press ENTER . (*)3 Type the Password: rd and Press ENTER . (*)Results: The WESMAINT II+ Main Menu appears.4 If a time-out occurs, press ENTER again, to return to login prompt.WESMAINTTips• User name and password shown are factory defaults. If you cannot log in,contact your system administrator to obtain new user name and password.• To select an option from the menus, use the up and down arrow keys to highlightand item and press ENTER , or type the menu item number.• Press C TRL+L at any time to log out of WESMAINT II+.• For further information, see the WESMAINT II+ User’s Guide