D25User's Manual GE Grid Solutions28 994-0081-3.00-21 GE InformationSet Up of a Color GDP (CGDP)Overview This section describes how to set up the Color Graphical Display Panel(CGDP) on your D25*. The CGDP uses a licensed software package namedthe GDP 300 from Quasar Controls, which you must register as part of thesetup procedure. The CGDP software includes system firmware named theSubstation Bay Viewer™ 300 (SB Viewer 300) that runs on the D25 CGDPand a Windows-based editor named the Substation Bay Config Tool™ 300(SBC Tool 300) that runs on a PC.The diagram below shows the relationship between the PC, D25 and CGDP(SB Viewer 3 00). The SB Viewer 300 and D25 communicate with eachother using the DNP protocol over RS-485. The SB Viewer 300 is configuredusing the SBC Tool 300 running on the PC. The D25 is configured usingSGConfig which also run on the PC.PCSGConfig SBC Tool300D25 CGDPRS-485D25 ConfigurationSB Viewer 300(DNP DCA)DNP PACKETsSB Viewer 300 ConfigurationDNP DPAPrerequisites Install the:• Compact Flash Card (GE part number 160-0125) which includesWindows Embedded CE and SB Viewer 300• SBC Tool 300 in Windows 7 or Windows Server 2008