905.019.1 Installation and connecting–up regulations9-341© Siemens AG 2012 All Rights ReservedSIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition9.1.2 Mounting conditions, internal coolingNoteThe regulations described in the ”SINAMICS S120 Booksize / SIMODRIVESystem Manual” switchgear cabinet integration system manualOrder No.: 6SL3097–0AT00–0AP must be observed for the heat dissipation!If the guidelines for installing/mounting SIMODRIVE 611 equipment in the cabi-net are not carefully observed, this can significantly reduce the service life of theequipment and result in premature component failure.The following specifications must be carefully observed when mounting/instal-ling a SIMODRIVE 611 drive group: Cooling clearance Cable routing Air flow, climate–control equipmentMinimum 100 mm clearance at the top and bottom for cooling.ÄÄÄÄÄÄÄÄÄÄÄÄChannel cableIncorrect CorrectÄÄÄÄÄÄÄÄÄÄÄÄ40 mm40 mm80 mmSIMODRIVE 611Cooling clearancetop and bottom100 mm100 mmSIMODRIVE 611100 mmFig. 9-4 Cooling clearanceAir intake temperature, max 40 °C, at higher temperatures (max 55 °C), thepower must be reduced (derating).GeneralinformationCooling clearance9 Cabinet Design and EMC05.08