Panasonic Eco Solutions Nordic ABMEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x14531.5 Acknowledge SERVICE signal (H8/S4)See chapter "Sensors activating SERVICE signal (H4/U6)", page 122.When service signal from a sensor is acknowledged, the sensor isgiven a default sensor value (for a new / clean sensor), i.e. firstreplace the sensor, then acknowledge the service signal as soon aspossible.The first week average sensor value (after acknowledge) will becalculated within one hour and thereafter each week.NOTE! If a sensor is replaced without having generated servicesignal, it has to be reset to the default sensor value, see chapter "Clearweekly average (H8/S5)", page 146.Action Text in display Comments"Access" According to chapter"Access code formaintenance", see page141.Scroll to menu S4. Acknowledge SERVICE signalACCEPT? S4"A" Sensor : xxxxxx needs serviceLNOTE! The list order in this menu is as follows:a) Technical number order in the control unit this menu isopened.b) Technical number order in the rest of the system.If there are no sensors toacknowledge, menu S4will be shown again.L = a list in which you canscroll. If it is the correctsensor to acknowledge,press "Fault acknowledge".If not, scroll or write thewanted sensor and press"Fault acknowledge" orpress "Return" to S4."Fault acknowledge" The service signal for that sensor is now acknowledged andthe next sensor will be shown in the display.Sensor : yyyyyy needs serviceLIf more service signalacknowledgements shallbe done, continue likeabove. If not, press"Return" to menu S4."Return" Acknowledge SERVICE signalACCEPT? S4Scroll or press "Return" tomenu H8. Scroll or press"Return" to log off.LED "Service" (L12) will be turned off when all sensors have beenacknowledged.