Panasonic Eco Solutions Nordic ABMEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x9825.2 Disable zone / address (H2/B2)Addressable alarm points (also addressable manual call points),connected to the COM loop, can be individually disabled.Disabled alarm points, zone / addresses, are listed in menu H4/U1from which it is also possible to get a print-out.Regarding disabled analog smoke detector: The sensor values will notbe saved, i.e. only the values saved before and after the disablementwill be used when calculating the week average sensor value.Disabled alarm points, zone / addresses, have to be re-enabled viamenu H4/B2.Action Text in display Comments"Access" According to chapter"Access", see page 92.Scroll to menu H2. Disable or re-enableACCEPT? H2"A" Disable zoneACCEPT? B1Scroll to menu B2. Disable zone / addressACCEPT? B2"A" Disable zone: 000 Address: 00ACCEPT?Write zone number andaddress(e.g. 001 / 01)Disable zone: 001 Address: 01ACCEPT?Press "A" to accept."A" Automatic re-enabling:0 (0=No,1=Yes)Time: HH:MM ACCEPT?(Default is current time + 3 hours)Press "1" for aut. re-enabling and accept orchange the time (max. 24hours). Press "A" toaccept. LED"Disablements" (L8) willlight up."A" Disable zone: 000 Address: 00ACCEPT?If more disablementsshall be done, continuelike above. If not, press"Return" to menu B2.Scroll or press "Return"to menu H2. Scroll orpress "Return" to log off.