Panasonic Eco Solutions Nordic ABMEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x13128.6 Display current consumption in unit(H5/A5)The resolution is not very high, i.e. the displayed values give only arough idea of the current consumption.Control unit: The total current consumption (including the chargingcurrent at 24V) for the selected control unit (c.i.e.) when it isconnected to the mains (230 V AC), i.e. this function is not workingby battery backup.Charging: The battery charging current for the selected control unit(c.i.e.). This is at 24 V, i.e. before the DC/DC converter for batterycharging voltage etc.NOTE! Control unit current >3800 mA is presented as >3800mA.Charging current <100 mA can not be correctlypresented.The displayed "Charging" value (xxxx mA) shall bemultiplied by two when "High current charging mode"has been selected via jumper "JP2" on the Charger board1657. (JP2 shunted = High current charging mode.)Action Text in display Comments"Access" According to chapter"Access code for service(H5)", see page 126.Scroll to menu A5 Display current consumption in unitACCEPT? A5"A" From which control unit shall currentconsumption be displayed: 00 ACCEPT?Write control unit number.Press "A" to accept."A" Wait......No reply from control unit..... If the control unit don'texist or don't answer, thismessage will be shown.Current consumption control unit 00Control unit: xxxx mA Charging: xxxx mA"A" Display current consumption in unitACCEPT? A5Scroll or press "Return" toH5. Scroll or press"Return" to log off.