Panasonic Eco Solutions Nordic ABMEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x12327.7 Event log (H4/U7)This is a list of events. Type and number of events in the list, etc. canbe set in Win512 (see Planning Instructions and Win512 help).From this menu, it is possible to get a print-out.The events can be listed:Via display: See Alternative "A" below.Via a print-out: See Alternative "1" below.NOTE! The event logging is disabled as long as menu H4/U7 isopen.Action Text in display Comments"Access" According to chapter"Access", see page 92.Scroll to menu H4. Present system status on display andprinter ACCEPT? H4"A" DisablementPrintout: (1=yes) U1Scroll to menu U7. Event logPrintout: (1=yes) U7Press "A" for displaypresentation orPress "1" for print-out.Alternative "A" When "A" is pressed, an event will be shown in the display,e.g:FIRE ALARM zone 123 address 45MM-DD HH:MM XXorFIRE ALARM zone 456Many alarms in zone MM-DD HH:MM XXThe most recent eventwill be shown, i.e. use"" to scroll upwards inthe list. Press "Return"to menu U7.(XX in the example =control unit number.XX=99=Win512).Alternative "1" How many events should be printed? 000ACCEPT?Write number of eventsto be printed,e.g. "010"How many events should be printed? 010ACCEPT?Press "A" to start print-out."A" Printing started. To stop printing pressC and 0 simultaneously. ACCEPT?"A" Show event logPrintout: (1=yes) U7Scroll or press "Return"to menu H4. Scroll orpress "Return" to log off.A) More than one alarm point in zone 456 have activated fire alarm.