Panasonic Eco Solutions Nordic ABMEW01457 Rev: - Operating Instructions Fire alarm system EBL512, V2.7.x10325.6 Re-enable control output (H2/B6)Disabled outputs are listed in menu H4/U1 from which it is alsopossible to get a print-out.When all control outputs have been re-enabled, The LED"Disablements" (L8) will be turned OFF, if there are no otherdisablements in the system.Action Text in display Comments"Access" According to chapter"Access", see page 92.Scroll to menu H2. Disable or re-enableACCEPT? H2"A" Disable zoneACCEPT? B1Scroll to menu B6. Re-enable control outputACCEPT? B6"A" Re-enable control output type: 00=Loopunit 1=S 2=R 3=RE 4=ES ACCEPT?(4=ES not valid in Swedish (SBF) convention)Press:"0"=RU4 (2265) orSU4 (2262 / 2263) orMIO (3361) orASI (3377) orASB (3378)"1"=S0-S3"2"=R0-R1"3"=Relay board 1581"4"=1583 board output"Extinguishing system".Press "A" to accept."A"Depending on thechosen type, 0, 1, 2, 3resp. 4, the followingwill be shown:Re-enable 00 0000 output 0ACCEPT? LRe-enable control unit 00 S0ACCEPT? LRe-enable control unit 00 R0ACCEPT? LRe-enable control unit 00 relay board 0output 0 ACCEPT? LRe-enable output for extinguishingsystem on 1583 board, CU 00 ACCEPT? LIf there are no outputs tore-enable, menu B6 will beshown again.L=a list in which you canscroll.Regarding the ASI (3377)& ASB (3378) units:Output:0=high priority1=medium priority2=low priorityIf it's the correct output tore-enable, press "A" toaccept. If not, scroll orwrite the wanted outputand press "A" to accept.