ZX Fire Alarm Control Panels MORLEY-IASCommissioning Manual Document No. 996-175-000-1, Revision 01 Page 5314.1.1 General Events• This option allows special system-event operation on several general functions as shown below. Anyitem set to event ‘0’ means that this item is not in use.General System Event Name When the event is generatedFault Event Detection of a faultPre-Alarm Event Any detector entering a pre-alarm conditionDelayed Day mode Event Detection of a fire in a delayed-day modeLocal Fire Event Any detector connected to the panel enteringa fire conditionCommon Fire Event Any panel connected to a Master entering afire condition.Silence Event (1) When the external alarms are silencedSimple Co-incidence Event When any 2 devices enter a fire condition.(This is independent of device type).AC Fail Event When the AC fail timer has expired (1 minute)Reset Event (2) Generated when the panel is reset.General Disablement Event (3)(available in software version 830onwards)Active whenever the control panel’s generaldisablement indicator is illuminated.Table 15 – General System Events(1) The silence event is automatically created as non-latching. The event is removed whensilence is cancelled (e.g. by re-sounding the alarms or resetting the panel).(2) A reset event is transient. It is removed 15s after the panel has reset.(3) A general disablement event is not transmitted across the network, though the sameevent number can be assigned on each panel – giving the same effect. An outputassociated with a general disablement event may briefly de-activate on a reset beforere-asserting itself – until the event is cleared.14.1.2 Event Logic• The System event logic allows complex logic sequences to be programmed into the fire panel.• The logic modes support both ‘AND’ (coincidence) and ‘OR’ functions on events, together with timersadjustable in 1 second steps up to 1800 seconds.• A PC is essential for programming event logic.• The ‘Logic’ display allows any event sequence uploaded from the PC to be inspected on the Panel.