ZX Fire Alarm Control Panels MORLEY-IASCommissioning Manual Document No. 996-175-000-1, Revision 01 Page 43NOTE: Only one mode of operation can be selected to be operational at one time.11.2 Delayed ModeEN54!EN54-2 7.11Delays to Outputs• The panel can be configured to operate in a delayed modeduring the daytime in any specified zone.• During this time, high sensor signals will generate a firemessage at the panel, but delay the output to the sounders. Thepanel will initiate a full fire alarm if action is not taken on thiswarning within a specified time.• Manual call points (Pull Stations) will always generate animmediate fire alarm, regardless of any day mode setting.• Ensure that at least one sounder circuit is configured for immediateoperation when the fire alarm is confirmed (end of stage 2 time).• Ensure that the fire output relay is configured with theappropriate pattern so that it does NOT turn on until the firealarm is confirmed (end of stage 2 time).11.2.1 Commissioning Delayed Mode• Press ‘1’ to select Delayed mode from the Day Mode Menu. The display will prompt whether the modeis to be used.[ Panel in Commissioning mode ]---------------------------------------------Allow mode ?• Press ‘No’ to inhibit the mode and return to the Day Mode menu.• Press ‘Yes’ to enable the mode. The display will then prompt the start and end times for the day period.[ Panel in Commissioning mode ]---------------------------------------------START at 08:45 ?• Press ‘Yes’ to accept and step on. Press ‘No’ to change and then enter the required start time usingthe number buttons.[ Panel in Commissioning mode ]---------------------------------------------START at 08:45 FINISH at 16:35 ?• Press ‘Yes’ to accept and step on. Press ‘No’ to change and then enter the required end time using thenumber buttons. Note: the delay mode will remain active for the extent of the ‘FINISH at’ minute.• A two-stage timer is built into the day mode.• After entry of the start / end times, the display prompts the stage timers as follows: