MORLEY-IAS ZX Fire Alarm Control PanelsPage 16 Document No. 996-175-000-1, Revision 01 Commissioning Manual5.2.1 Auto Learn• This facility saves considerable time and effort when installing a system, or when changing sensorconfiguration. It allows the system to learn for itself what devices have been installed on a particular loop.• Press ‘3’ from the CONFIGURE menu to select ‘Auto Learn’. The display will respond with the message:[ Panel in Commissioning mode ]----------------------------------------------Auto Learn finds ALL device addressesand types on loop 1. Shall I do this ?5.2.1.1 Full Auto Learn• To proceed with ‘Auto Learn’, press the ‘Yes’ key. The system will confirm your command with themessage ‘Program running’ on the display. It may take several minutes to learn a complete loop. Eachpossible sensor address is checked to see if any detector is installed at that address. If a detector has beeninstalled, the panel determines the type of the detector. If more than one detector is located at a singleaddress, or the detector type code is invalid, a warning message will appear on the display.• Do not press any key until the display changes from the ‘program running’ message.• Once the system has finished learning, it will respond with a display giving a summary of the detectorsfound on the loop. For example.[ Panel in Commissioning mode ]---------------------------------------------Ion Opto Temp Sounder MCP Zone-Mon Other37 24 2 8 14 2 3• This display should be checked, against the installation sheets, to ensure that the system has foundthe correct number of devices.• Pressing any key then restores the display to the normal commissioning menu.• The Auto Learn sequence should be repeated for each loop on the system. It can be used as many timesas required and does not affect the text description used to describe the location of each sensor.Always verify that the system has found all devices correctly. Use the ‘Devices’ option toobtain detailed information on the device type and to see the address of each devicefound on the loop.5.2.1.2 Quick Status Check• To perform a ‘Quick Status Check’, press the ‘No’ key instead when prompted to perform the AutoLearn. The system will respond immediately with a display giving a summary of the detectors alreadyprogrammed for this loop. For example.[ Panel in Commissioning mode ]---------------------------------------------Ion Opto Temp Sounder MCP Zone-Mon Other37 24 2 8 14 2 3