MORLEY-IAS ZX Fire Alarm Control PanelsPage 46 Document No. 996-175-000-1, Revision 01 Commissioning ManualThe alarm verification feature should not be used as a substitute for proper detectorlocation/applications or regular system maintenance. Alarm verification features areintended to reduce the frequency of false alarms caused by transient conditions. They arenot intended to compensate for installation design errors or lack of maintenance.Keep the verification delay to a minimum. A maximum delay of 5 secs is recommended.11.4.1 Commissioning Verification Mode• Press ‘3’ to select Verification mode from the ‘Day Modes Menu. The display will prompt whether themode is to be used.[ Panel in Commissioning mode ]---------------------------------------------Allow mode ?• Press ‘No’ to inhibit the mode and return to the ‘Day Mode’ menu.• Press ‘Yes’ to enable the mode. The display will then prompt the start and end times for the day period.[ Panel in Commissioning mode ]---------------------------------------------START at 6:30 ?• Press ‘Yes’ to accept and step on. Press ‘No’ to change and then enter the required start time usingthe number buttons.[ Panel in Commissioning mode ]---------------------------------------------START at 6:30 FINISH at 17:45 ?• Press ‘Yes’ to accept and step on. Press ‘No’ to change and then enter the required end time usingthe number buttons. The display then prompts how long to delay the alarm.[ Panel in Commissioning mode ]---------------------------------------------Verification delay = 0 s ?• Enter the desired delay (see above guidelines for maximum times).When the event log is set to ‘Normal’ the panel will record the high, analogue outputsignal from the detector that initiated the verification timer. If the detector is still in alarmat the end of the verification delay, a fire alarm will be recorded in the log. With the eventlog in ‘Diagnostic’ the panel will record all analogue signals received from the detectoruntil the smoke level drops back to normal.