67d3.28 Analog_Speed_Con Chooses analog-speed channels0: Invalid analog channel1: Valid analog channel 1 (AIN1)2: Valid analog channel 2 (AIN2)10~17:AIN1 for ―Din_Speed (X-10)‖20~27:AIN2 for ―Din_Speed (X-20)‖Valid in mode -3, 3 and 1.0 0~210~1720~27d3.29 Analog_Speed_Factor Sets the proportion between analog signalsand output speed0 /d3.32 Analog_MaxT_Con 0: No control1: Max torque that Ain1 can control2: Max torque that Ain2 can control0 0~2d3.33 Analog_MaxT_Factor Indicates the max torque factor for analogsignal control8192 0~327677.2.3 Analog Signal ProcessingFig. 7-8 Analog signal processingElectrical control on internal variables is available only after ADC conversion and offset of external analogsignals, and judgment of dead zone signals.For offset processing, see the left part in Fig. 7-6; for dead zone processing, see the right part in Fig. 7-6.7.2.4 Examples of Analog – Speed ModeIn the analog – speed mode, follow the steps below to set a driver:Step 1: Confirm whether it is necessary to enable the driver through external digital input ports. To enable thedriver through external digital input ports, see Table 6-12 in Example 6-3 for settings. If the driver does notrequire enabling through external digital input ports, you can disable the enabling function of external digitalinput ports by referring to Table 6-13 of Example 6-3, and enable the auto power-on function of the driver bysetting its internal parameters.Step 2: Confirm whether limit switches are required. By default, the driver operates in the limit status after2047-2048shiftU-10v10v102047-20482deadU-10v10vexternalUexternalUernalUinternalUintOffset Dead zone