98 MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016Circuit Mapping and Cross-Zoning Input-to-Output Circuit Mapping and Cross-Zone OperationExample 4: A dual hazard, cross-zoned application using four input zones and two releasing outputcircuits. Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed asRELEASE 1. Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which isprogrammed as a RELEASE 2.• Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.• Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.• Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus• Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.• Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (AlarmNAC) but not Output Circuits 2, 3 or 4.• Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate OutputCircuit 2 (Release 1) but not Output Circuits 3 or 4.• Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate OutputCircuit 3 (Release 2) but not Output Circuits 2 or 4.ZONE 1 TYPE1=WATERFLOW NS2=COMBO3=COMBO W/AR. SUPERVOUTPUT MAP ZONE 11=ALARM NAC YES2=RELEASE 1 YES3=RELEASE 2 NOOUTPUT MAP ZONE 11=SUPV BELL NAC N/AREL 1 CROSS GROUP 11=ZONE 1 YES2=ZONE 2 YES3=ZONE 3 NOOUTPUT MAP ZONE 21=SUPV BELL NAC N/AZONE 2 TYPE1=WATERFLOW NS2=COMBO3=COMBO W/AR. SUPERVOUTPUT MAP ZONE 21=ALARM NAC YES2=RELEASE 1 YES3=RELEASE 2 NOZONE 3 TYPE1=WATERFLOW NS2=COMBO3=COMBO W/AR. SUPERVZONE 4 TYPE1=WATERFLOW NS2=COMBO3=COMBO W/AR. SUPERVOUTPUT MAP ZONE 31=ALARM NAC YES2=RELEASE 1 NO3=RELEASE 2 YESOUTPUT MAP ZONE 31=SUPV BELL NAC N/AOUTPUT MAP ZONE 41=SUPV BELL NAC N/AOUTPUT MAP ZONE 41=ALARM NAC YES2=RELEASE 1 NO3=RELEASE 2 YESREL 2 CROSS GROUP 11=ZONE 1 NO2=ZONE 2 NO3=ZONE 3 YESREL 2 CROSS GROUP 11=ZONE 4 YES2=ZONE 5 NO3=ZONE 6 NO