18 MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016Product Description Components• Fire Alarm - red indicator• Supervisory - yellow indicator• AC Power - green indicator• System Trouble - yellow indicator• Alarm Silenced - yellow indicator• Discharge - red indicator• Pre-discharge - red indicator• Abort - yellow indicatorLocal Piezo SounderA piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervi-sory conditions as follows:• Alarm - on steady• Trouble - pulse 1 second on and 1 second off• Maintenance - pulse ½ second on and ½ second off• Supervisory - pulse ½ second on and ½ second off1.4 ComponentsMain Circuit BoardThe main circuit board contains the system’s CPU and other primary components and wiring inter-face connectors. Optional modules plug in and are mounted to the main circuit board.Power SupplyOne FLPS-7 power supply is provided standard with each FACP, mounted to a chassis.CabinetThe backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and providesspace for two batteries (up to 18 Amp Hours). Also available are the optional dress panel DP-51050[red] and trim-ring TR-CE [red]. The Canadian version is supplied standard with a modified dresspanel and one ANN-LED annunciator module.BatteriesThe cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a ULlisted battery box such as the BB-55F or BB-26). Batteries must be ordered separately.1.5 Optional Modules and AccessoriesCAC-5X Class A Converter ModuleThe CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits toStyle D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connectto J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are requiredto convert all six Initiating Device Circuits and four Output Circuits.4XTMF Transmitter ModuleThe 4XTMF provides a supervised output for local energy municipal box transmitter and alarm andtrouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumperoption allows the reverse polarity circuit to open with a system trouble condition if no alarm condi-tion exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.ANN-SEC Secondary ANN-BUS ModuleThe ANN-SEC module provides another ANN-BUS port for more wiring flexibility and forCanadian applications requiring remote annunciation.