Cut along dotted line.MRP-2002, MRP-2002E, MRP-2002C Agent Release Control SystemOperating InstructionsNORMAL - Only AC POWER is illuminated green.All other indicators are off. LCD display will read SYSTEM ALLNORMAL.PANEL KEY - The key to open the panel can be found at the followinglocation:________________________________________________________To return to normal after an alarm1. Do not enter the protected area until safe to do so.2. Clear all initiating devices. Smoke detectors will not reset if there isstill smoke in the area.3. Reset the control panel (PRESS the RESET button).Power failure or brownoutIf AC power drops too low or fails, the AC POWER indicator willextinguish, the system TROUBLE indicator will turn on yellow, and thepanel buzzer and any other audible trouble devices will sound. Contactauthorized service personnel immediately. See below.Manual ReleaseActivation of Manual Release Switch will override Predischarge Delayand override an active Abort Release Switch resulting in an immediateagent release.Manual activation (Fire Drill or otherwise)Notification Appliance Circuits (NACs) can be activated by pressing andholding the DRILL button for at least two seconds.NOTE: You may want to disconnect the municipal box bysliding the DISCONNECT switch, located on the 4XTMFmodule, to its disconnect position (to the right). If a DACT isconnected, notify the monitoring service before conductingany fire drills or tests.Alarm SilencingNotification Appliance Circuits may be silenced by pressing the ALARMSILENCE button. ALARM SILENCED will turn on yellow. Subsequentalarms will reactivate circuits. Press the RESET button to clear the"silenced" condition.NOTE: Notification Appliance Circuits may be programmedas nonsilenceable. Also, Signal Silence Inhibit, if enabled,will prevent silencing of NACs for one minute after an alarm(see manual).To test the indicators, LCD display and piezoPress and release the RESET button and check all indicators/LEDs.Every indicator/LED should be on, LCD shows all pixels on, piezosounder beeps.For more information, refer to the MRP-2002 Series Manual, Document#53049. It is kept in the following location:_______________________________________________________THIS SHEET SHALL BE FRAMED ADJACENT TOTHE CONTROL PANELWHEN AUDIBLE DEVICES ARE SOUNDING -Discharge has occurred if DISCHARGE Indicator is on.Discharge timer has timed out if the DISCHARGE Indicator is flashing.FOR AN ALARM1. Evacuate the protected area2. Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what your current status is.Phones: ________________________________________ _____________________________________________Fire Department Monitoring Service3. If the Fire Department is responding, be prepared to provide directions to arriving firefighters.FOR TROUBLE ONLY1. Notify the monitoring service and/or Fire department if this panel is connected to either one, and tell them what is happening.2. Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE/STEP button. The TROUBLE indicator willremain illuminated yellow. Contact authorized service personnel immediately! (See Below).WARNING!DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM. THE PROTECTION THESYSTEM OFFERS HAS BEEN COMPROMISED OR ELIMINATED, WHEN A TROUBLE CONDITION EXISTS.In the event of trouble, contact thelocal Fire-Lite Service RepresentativeName: _____________________________________Company: __________________________________Address: ___________________________________Telephone Number: __________________________ Document #53075 Rev. B 2/7/11 ECN 10-015