MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016 59Master Programming Level ProgrammingNote that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is enabled.The exception is when a Release Circuit is disabled, a supervisory will be logged on the FACP untilthe circuit is enabled.TypePressing 2 while viewing Output Screen #1 will cause the following screen to be displayed:Pressing the down arrow key while viewing the Edit Output Type Screen will display additionalscreens with the following types:• Release Circuit 1• Release Circuit 2• Alarm NAC• Waterflow NAC• Release Stage Coded NAC (Refer to “Release Stage/NAC Operation” on page 85.)• Release Stage Discharge NAC (Refer to “Release Stage/NAC Operation” on page 85.)• Release Stage Pre-Discharge NAC (Refer to “Release Stage/NAC Operation” on page 85.)• Horn NAC• Strobe NAC• Supv Bell NAC• Trouble Bell NACPress the number key corresponding to the desired Output Type to program the selected Output. Release Circuit 1 or Release Circuit 2If Release Circuit 1 or Release Circuit 2 is selected as the Output Type, the following subscreenwill be displayed:This screen allows the programmer to select whether or not to supervise the Releasing CircuitOutput for shorts.• UNSUPV SHORTS - this option should normally be selected when a releasing solenoid isconnected to the output so the solenoid coil is not supervised for shorts• SUPV SHORTS - this option, which supervises for shorts, should only be selected when theREL-4.7K option is installed in series with the solenoid coil.EDIT OUTPUT # TYPE1=RELEASE CIRCUIT 12=RELEASE CIRCUIT 23=ALARM NACEdit Output # Type ScreenEDIT RELEASE CIR #1=UNSUPV SHORTS2=SUPV SHORTSNOTE: Release circuits may be directly activated by a single input zone or may be activatedusing cross-zoned inputs. Refer to “Circuit Mapping and Cross-Zoning” on page 95 for adescription of cross-zoning and input to output circuit mapping.