MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016 69Master Programming Level Programming Daylight Savings TimePressing 1 while viewing Time-Date Screen #2 will cause the following screens to be displayed:Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle betweenEnabled Yes and Enabled No. The control panel will automatically update the time for daylightsavings time when Enabled Yes is selected.Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows theprogrammer to select the month that daylight savings time will begin. In this sub-screen, pressing 1will select March, 2 will select April and 3 will select May.Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow theprogrammer to select the week of the month that daylight savings time will begin. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the thirdweek, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select thelast week of the selected month.Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows theprogrammer to select the month that daylight savings time will end. In this sub-screen, pressing 1will select September, 2 will select October and 3 will select November.Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow theprogrammer to select the week of the month that daylight savings time will end. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the thirdweek, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select thelast week of the selected month.Trouble ReminderThe Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ foralarms and troubles, after the panel has been silenced. Refer to “System Setup” on page 64, for adetailed description of this feature. Pressing 2 while viewing System Setup Screen #2 will cause thedisplay to toggle to Trouble Remind Yes, which enables this feature. Each press of the 2 key willcause the display to toggle between Trouble Remind Yes and Trouble Remind No.Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for morethan 24 hours will cause the FACP to resound the trouble sounder.Charger DisablePressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or disablethe onboard battery charger. If an external battery charger is being used, the onboard batterycharger must be disabled. Each press of the 3 key will toggle between Chargr Disable No andChargr Disable Yes.Canadian OptionPressing 1 while viewing System Setup Screen #3 will configure the FACP to comply withCanadian requirements. The display will change to Canadian Opt. On. Each press of the 2 key willcause the display to toggle between Canadian Opt. On and Canadian Opt. Off. The factory defaultsetting is Canadian Opt. Off.The Canadian Options configures the FACP with the following as required by Canada:• The following zone type codes are not available: non-latching supervisory non-latching drillTIME AND DATE1=DAYLIGHT SAVINGSTime & Date Screen #2 DAYLIGHT SAVINGS1=ENABLED YES2=START MONTH MAR3=START WEEK WK 2Daylight Savings Screen #1 Daylight Savings Screen #2DAYLIGHT SAVINGS1=END MONTH NOV2=END WEEK WK 1SYSTEM SETUP1=TIME-DATE2=TROUBLE REMIND3=CHARGR DISABLESystem Setup Screen #2SYSTEM SETUP1=CANADIAN OPTION2=SEC ANN ENABLESystem Setup Screen #3