MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016 119Template 7: Cross-Zone System - Bell/Horn/Strobe FACP Configuration TemplatesB.7 Template 7: Cross-Zone System - Bell/Horn/StrobeTable Legend:* = shows relationship only, will not activate a release circuitX = direct correlation between Input Zone and Output Circuit (input zone activation will turn oncorresponding output circuit after any applicable delays).Xc = cross-zone output where X indicates a direct correlation between Input Zone and Output Cir-cuit (input zone activation will activate the corresponding output circuit) and c indicates that theoutput circuit will indicate when one or more inputs of a cross-zoned group have been activated(refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” on page 61).Cn = cross-zone inputs where n is the number of the Release Circuit. All inputs with the sameRelease Circuit number must be active at the same time to turn on the corresponding Release outputcircuit.Xr = release stage output where X indicates a direct correlation between Input Zone and OutputCircuit (input zone activation will activate the corresponding output circuit) and r indicates that theoutput circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to“Release Stage/NAC Operation” on page 85).Input Zone Types:• Zone 1 = circuit with type code of 2-wire smoke• Zone 2 = circuit with type code of 2-wire smoke• Zone 3 = circuit with type code Manual Release - activation will cause an immediate agentrelease• Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Typeoperation (refer to “Abort Type” on page 65)• Zone 5 = circuit with type code of Discharge Pressure Switch• Zone 6 = circuit with type code of SupervisoryOutput Circuit Types:• Output 1 = Release Circuit 1 - Supervised for shorts• Output 2 = Alarm NAC - silenceable, programmed for Cross-Zone Pre-Discharge codedoperation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit2:” on page 61)• Output 3 = Release Stage Coded - silenceable, programmed Release Stage Coded operation forRelease Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit 2:” onpage 61)• Output 4 = Release Stage Discharge - nonsilenceable, programmed Release Stage Dischargeoperation for Release Circuit 1 (refer to “Cross-Zone for Release Circuit 1 or Release Circuit2:” on page 61)Template 7: Cross-Zone System - Bell/Horn/StrobeINPUT ZONES1 2 3 4 5 6OUTPUT CIRCUITS 2-WIRESMOKE2-WIRESMOKEMANUALRELEASE ABORT DISCHARGEPRESSURE SUPERVISORY#1 RELEASE CIRCUIT 1 C1 C1 X X* X*#2 ALARM NAC Xc Xc#3 RELEASE STAGE CODED Xr Xr Xr Xr#4 RELEASE STAGEDISCHARGEXr Xr Xr Xr