32 MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016Installation Installation of Optional ModulesWiring NACs and IDCs for Class AWire the Style Z (Class A) Notification Appliance Circuits using TB5 of the FACP main circuitboard and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits usingTB4 of the FACP main circuit board and TB1 of the CAC-5X. Note that the wiring will be identicalwhen using TB7 NAC and TB6 IDC of the FACP. Make certain to observe polarity when connect-ing the devices to the circuits. The B+ and A+ terminals must comprise the feed and return for thepositive side of a device and the B- and A- terminals must comprise the feed and return for the neg-ative side of a device. To configure any of the zones for Class B when the CAC-5X is installed,simply wire to the B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistorafter the last device on the circuit. Do not wire to the corresponding A+ and A- terminals on theCAC-5X module.Figure 2.14 Wiring NACs and IDCs for Class A OperationCAC-5X Class A Converter ModuleFACP MainCircuit BoardClass B (Style B) IDC - 4.7 KΩ½ watt ELR resistorP/N:71252 (supervised and power-limited)Dummy load all unusedcircuits - 4.7 KΩ½ watt resistor(P/N: 71245)PolarizedBellCircuit polaritiesshown in alarmconditionClass A (Style Z) NAC(supervised and power-limited)Class A (Style D) IDC(supervised and power-limited)PolarizedStrobePolarizedHornSmokeSmokePull Station Pull StationHeat Heatms10udclassa.cdrB+ B- B+ B-A+ A- A+ A- A+ A- A+ A- A+ A- A+ A- A+B+ B- B+ B- B+ B- B+ B- B+