104 MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016FACP Configuration Templates Template 2: Single Zone System With HornB.2 Template 2: Single Zone System With HornTable Legend:X = direct correlation between Input Zone and Output Circuit (input zone activation will turn oncorresponding output circuit after any applicable delays).Xr = release stage output where X indicates a direct correlation between Input Zone and OutputCircuit (input zone activation will activate the corresponding output circuit) and r indicates that theoutput circuit will indicate one of three stages of a releasing operation by its pulse rate (refer to“Release Stage/NAC Operation” on page 85).Input Zone Types:• Zone 1 = circuit with type code of 2-wire smoke• Zone 2 = circuit with type code of 2-wire smoke• Zone 3 = circuit with type code Manual Release - activation will cause an immediate agentrelease• Zone 4 = circuit with type code of Abort Release Switch - programmed for UL Abort Typeoperation (refer to “Abort Type” on page 65)• Zone 5 = circuit with type code of Pull Station• Zone 6 = circuit with type code of SupervisoryOutput Circuit Types:• Output 1 = Release Circuit 1 - Unsupervised for shorts• Output 2 = Release Stage NAC - silenceable, programmed Release Stage operation (refer to“Release Stage/NAC Operation” on page 85)• Output 3 = Alarm NAC - silenceable, coded for steady on• Output 4 = Alarm NAC - silenceable, coded for steady onTimers• Pre-Discharge Delay - set for 30 seconds• Discharge - set for 1 minute• Waterflow Delay Timer - set for 90 seconds• AC Loss Delay Timer - set for 2 hoursTemplate 2: Single Zone System with HornINPUT ZONES1 2 3 4 5 6OUTPUT CIRCUITS 2-WIRESMOKE2-WIRESMOKEMANUALRELEASEABORT PULLSTATIONSUPERVISORY#1 RELEASE CIRCUIT 1 X X X X#2 RELEASE STAGE NAC Xr Xr Xr#3 ALARM NAC X#4 ALARM NAC X X X