MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016 37ANN-BUS Devices InstallationException: When using the ANN-RLY module, the installer must ensure that the maximum24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations: Wiring Distance Calculation Example:Suppose a system is configured with the following ANN-BUS modules:• 2 ANN-80 Remote LCD Annunciators• 1 ANN-S/PG Serial/Parallel Printer Interface Module• 1 ANN-I/O LED Driver ModuleThe total worst case current is calculated as follows:Using this value and referring to the Wiring Distance Table 2.1 on page 36, it can be found that theavailable options are: 463 feet maximum using 22 Gauge wire 1,172 feet maximum using 18 Gauge wire 1,866 feet maximum using 16 Gauge wire 2,953 feet maximum using 14 Gauge wireWire Gauge Ohms per 1,000 feet (Rpu)22 16.218 6.416 4.0214 2.54Wire Gauge Maximum Wire Length18 312 feet16 497 feet14 787 feet12 1,250 feetANN-80 Current Draw = 2 X 0.040 amps = 0.080 ampsANN-S/PG Current Draw = 1 X.0.040 amps = 0.040 ampsANN-I/O Current Draw = 1 X.0.200 amps = 0.200 ampsTotal Worst Case Current Draw = 0.320 amps