MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016 123Template 8: Single Hazard, Single Detector - Bell/Horn/Strobe FACP Configuration Templates• AC Loss Delay Timer - set for 2 hoursFACP Operation• Input Zone 1 (2-Wire Smoke) Activation:Output 1 (Release Circuit 1 will perform an agent release following a 30 second Pre-Dischargedelay and remains on until panel reset.Output 2 (Alarm NAC) will turn on steady until discharge, it will then turn off.Output 3 (Release Stage Coded) will pulse at 1/2 second on, 1/2 second off until discharge, itwill then turn on steady.Output 4 (Release Stage Discharge) will turn on steady upon discharge.• Input Zone 2 (2-Wire Smoke) Activation:Output 1 (Release Circuit 1 will perform an agent release following a 30 second Pre-Dischargedelay and remains on until panel reset.Output 2 (Alarm NAC) will turn on steady until discharge, it will then turn off.Output 3 (Release Stage Coded) will pulse at 1/2 second on, 1/2 second off until discharge, itwill then turn on steady.Output 4 (Release Stage Discharge) will turn on steady upon discharge.• Input Zone 3 (Manual Release) Activation only:Output 1 (Release Circuit 1) begins agent release and remains on until reset.Output 3 (Release Stage Coded) will turn on steady.Output 4 (Release Stage Discharge) will turn on steady.• Input Zone 4 (Abort Release Switch) Activation only:Pre-Discharge Timer will continue to count down until it reaches 10 seconds and then stop.Releasing the Abort Release Switch will allow the Pre-Discharge Timer to continue its countdown from 10 second. If the Abort Release Switch is again activated before the Pre-DischargeTimer reaches 0, the Timer will reset to 10 seconds and hold.• Input Zone 5 (Discharge Pressure Switch) Activation:Output 3 (Release Stage Coded) will turn on steady.Output 4 (Release Stage Discharge) will turn on steady• Input Zone 6 (Supervisory) Activation:No output circuits will be activated. FACP will indicate a supervisory conditionFACP Relay OperationThe following description of FACP relay operations are in addition to normal system operation.• Alarm Relay (Latching) - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-WireSmoke) or Zone 3 (Manual Release) or Zone 5 (Discharge Pressure Switch) will operate AlarmRelay• Trouble Relay (Tracking) - any system trouble will activate the Trouble Relay• Supervisory (Tracking) - activation Input Zone 6 (Supervisory), the disabling of ReleasingCircuit or any other system supervisory will operate the Supervisory Relay