102 MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016FACP Configuration Templates Template 1: Cross-Zone System - With HornFACP Operation• Input Zone 1 (2-Wire Smoke) Activation only:Output 2 (Horn NAC) will pulse 1 second on and 1 second off.Output 4 (Alarm NAC) will turn on steady.• Input Zone 2 (2-Wire Smoke) Activation only:Output 2 (Horn NAC) will pulse 1 second on and 1 second off.Output 4 (Alarm NAC) will turn on steady.• Input Zone 3 (Manual Release) Activation only:Output 1 (Release Circuit 1) begins agent release and the Discharge Timer will begin to countdown. When the Discharge Timer reaches 0, Output 1 will turn off the agent releaseOutput 2 (Horn NAC) will turn on steadyOutput 4 (Alarm NAC) will turn on steady• Input Zone 4 (Abort Release Switch) Activation only:Pre-Discharge Timer will continue to count down until it reaches 10 seconds and then stop.Releasing the Abort Release Switch will allow the Pre-Discharge Timer to continue its countdown from 10 second. If the Abort Release Switch is again activated before the Pre-DischargeTimer reaches 0, the Timer will reset to 10 seconds and hold.• Input Zone 5 (Pull Station) Activation only:Output 1 (Release Circuit 1) begins agent release and the Discharge Timer will begin to countdown. When the Discharge Timer reaches 0, Output 1 will turn off the agent releaseOutput 3 (Alarm NAC) turns on steady• Input Zone 6 (Supervisory) Activation only:No output circuits will be activated. FACP will indicate a supervisory condition• Input Zone 1 (2-Wire Smoke) and Input Zone 2 (2-Wire Smoke) Activation together:In addition to the individual events that will occur for each Input Zone as detailed above, thePre-Discharge Timer will begin to count down. Output 2 will pulse at a ½ second on and ½second off rate while the Pre-Discharge Timer is counting down. When the Pre-DischargeTimer reaches 0, Output 1 (Release Circuit 1) will begin the agent release, Output 2 will turnon steady and the Discharge Timer will begin to count down. When the Discharge Timerreaches 0, Output 1 will turn off the agent release.FACP Relay OperationThe following description of FACP relay operations are in addition to normal system operation.• Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (2-Wire Smoke) or Zone 3(Manual Release) or Zone 5 (Pull Station) will operate Alarm Relay• Trouble Relay - any system trouble will activate the Trouble Relay• Supervisory - activation Input Zone 6 (Supervisory), the disabling of Releasing Circuit or anyother system supervisory will operate the Supervisory Relay