GX-Series Control Panel Installation and Setup Guide6-3447.1 ServiceThis option enables type 3.6 users to control the access mode of the remote servicing package. There areseveral options available for increased flexibility and security.0 = INT TelecomsThis option selects the on-board telecoms as the communication device.0 = Direct AccessOn selecting this option, a 40 minute access period is enabled on the GX-Series panel; remoteservicing software can directly access the system during this period. Once access to the panel hasbeen gained, it can be maintained indefinitely; there is no maximum duration. On terminating theremote servicing connection to the panel, the access period remains valid for an additional 15minutes.1 – 5 = Call Back 1 – 5A maximum of five numbers can be preprogrammed by the engineer (refer to option 56.1.12 =COMMUNICATIONS.Telecom.Remote Access). On selecting one of the numbers (1 – 5) followedby the ent key, the GX-Series panel dials out to the preprogrammed telephone number associatedwith the Call Back number.If the number selected does not have a preprogrammed telephone number, the system prompts for anumber 1 to be entered. Enter the required telephone number and press the ent key; the panel thendials out to the telephone number entered.NOTE: The PC that the panel is dialing to must have remote servicing software running in the Waitingfor Call-Back mode.1 = NOT USED2 = Ethernet0 = Direct AccessSee INT Telecoms description.1 – 5 = Call Back 1 – 5See INT Telecoms description (except menu option 56.4.03 replaces 56.1.12).3 = NOT USED47.2 Send AlarmsOption not available47.3 Call GX-SeriesOption not available47.4 Auto ServiceThe GX-Series panels can be programmed to automatically initiate communications to remote servicingsoftware, under three circumstances:• If any site programming has changed the panel will automatically send the new programming to thedownloader.• On a predetermined schedule the panel can activate an automatic periodic upload.• On a predetermined schedule the panel can activate an automatic remote routine inspection.NOTE: The Auto Service function works for both the Internal Telecoms and Ethernet module.The following sub options allow the engineer to select the mode of the automatic communication in each ofthe three situations. These options are not available to users.1 = ModeThis selects the mode of the automated connection following a change to the panel programming. There arefour modes: