INSTALLATION INSTRUCTIONS33-00360EF-05HPZC10*HONEYWELL HYDRONIC PROZONE VALVE CONTROL PANELWHAT'S IN THE BOX?• Hydronic Zone Panel• Mounting Hardware (3 Screws and 3 Wall Anchors)• 2, 2-Amp Fuses• Install Manuals (English & French)CAUTION1. Disconnect power supply before beginninginstallation to prevent electrical shock orequipment damage.2. Use copper conductors only.3. Use only NEC Class 1 wire for all line voltagewiring connections. Class 1 wires must berated for at least 167 °F (75 °C).4. For installation by professionals only.PANEL SPECIFICATIONSTable 1.1Each transformer is protected with a 2 Amp replaceable fuse.2Transformers have a Class 2 output and are rated for 24V, 40VA at 25 °C. It is up to the installer to ensure that the 40VAtransformer rating is not exceeded.3All circulator relay connections are rated for 5A full load and 30A locked rotor (1/6 to 1/2HP depending on technology)at 120VAC. Check circulator plate ratings to ensure full load current is not exceeded.Model Zones Transformers 1 Input PowerElectrical Rating forMain Burner, EndSwitch Burner, andZones2Electrical Rating forPump End Switch andPriority Pump 3PriorityZoneControlType 1 EnclosureWidth Height DepthHPZC103 3 (1) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC5FLA, 30LRAYes 10-1/4" 7-1/2" 2-1/8"HPZC104 4 (1) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC5FLA, 30LRAYes 10-1/4" 7-1/2” 2-1/8"HPZC105 5 (2) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC5FLA, 30LRAYes 11-3/4" 7-1/2" 2-1/8"HPZC106 6 (2) 24V 40VA 120VAC, 60Hz, 1 24V, 1 A 120 VAC5FLA, 30LRAYes 11-3/4" 7-1/2" 2-1/8"