VISTA-32FB/VISTA-128FB Installation and Setup Guide5-6FIELD TITLE and DATA ENTRIES EXPLANATION077670 Pager Phone Number forSupervisionEnter 0-9; #11 for *, #12 for #, #13 for a 2-second pause.Enter the paging service phone number for Trouble reports. Enter up to 17digits. Do not fill unused spaces.077680 Pager ID Number for SupervisionEnter 0-9Enter the Pager ID number for Trouble reports. Enter up to 10 digits.077690 Pager Phone Number forBypassesEnter 0-9; #11 for *, #12 for #, #13 for a 2-second pause.Enter the paging service phone number for Bypass reports. Enter up to 17digits. Do not fill unused spaces.077700 Pager ID Number for BypassesEnter 0-9Enter the Pager ID number for Bypass reports. Enter up to 10 digits.077710 Pager Phone Number forOpens/ClosesEnter 0-9; #11 for *, #12 for #, #13 for a 2-second pause.Enter the paging service phone number for Open/Close reports. Enter up to17 digits. Do not fill unused spaces.077720 Pager ID Number forOpen/ClosesEnter 0-9Enter the Pager ID number for Open/Close reports. Enter up to 10 digits.077730 Pager Phone Number for SystemEnter 0-9; #11 for *, #12 for #, #13 for a 2-second pause.Enter the paging service phone number for System reports. Enter up to 17digits. Do not fill unused spaces.077740 Pager ID Number for SystemEnter 0-9Enter the Pager ID number for System reports. Enter up to 10 digits.077750 Pager Phone Number for TestEnter 0-9; #11 for *, #12 for #, #13 for a 2-second pause.Enter the paging service phone number for Test reports. Enter up to 17 digits.Do not fill unused spaces.077760 Pager ID Number for TestEnter 0-9Enter the Pager ID number for Test reports. Enter up to 10 digits.077790 Zone Type Restores for ZoneTypes 1-80 = disable1 = enableThis field has eight entries, one for each zone type. Select the zone types thatwill send Restore reports.077800 Zone Type Restores for ZoneTypes 9 & 100 = disable1 = enableThis field has two entries, one for each zone type. Select the zone types thatwill send Restore reports.077830 First Test Report TimeEnter 00-07the for day (01 = Monday)Enter 00-23 for the hourEnter 00-59 for the minutesEnter the day and time that the first Test report shall be transmitted. Enter 00in all locations if the Test report is to be sent immediately upon exiting. Enter00 in the day location if the report is to be sent at the next occurrence of thetime that is set.077840 Swinger Suppression (partition-specific)Enter 01-15.Enter 00 for unlimited reportsThis option limits the number of messages (alarms or troubles) sent for aspecific zone in an armed period. The system automatically resets theshutdown for a zone after 48 hours if there are no trips on any zone.Must be 00 for UL commercial fire and burglary installations.