66 model 2000 DeviceNet Module Manual (DN611/DN611A)Chapter 4 Operating Procedures for the DN611 (Software)4Example: Input/output data setting information for node address = 1• Input data offset indicates the offset address (in bytes) from the top (0000H) of inputdata area.• Output data offset indicates the offset address (in bytes) from the top (0080H) ofoutput data area.• There are no items for bit strobe output data offset and number of bytes because thereis a bit strobe output data area.(14)Local station node address (010AH: 1 word)The node address of the local station set with the rotary switches on the side of themodule is stored in hexadecimals. (00H to 3FH).(15)Network communication rate (0109H: 1 word)The network communication rate set with the DIP switches on the front panel isstored.00H: Unassigned (setting disabled)01H: 500kbps02H: 250kbps03H: 125kbps(16)Operation mode on a Busoff (0108H: 1 word)DN611 operation mode data on the DN611's detecting a local station busoff is stored.00H: When a busoff is detected, the module will be set to standby mode, followed bythe initialization of the CAN controller.The procedure for resuming transmission is the same as in starting ordinarytransmission. Chapter 5 describes the transmission starting procedures.01H: When a busoff is detected, the module is left in the same operation mode whilethe CAN controller is initialized, followed by resumption of communication, ifpossible.(17)Supplying network power Yes/No (0107H: 1 word)Network power supply mode is stored.00H: Network power supply normal01H: Network power supply abnormalTable 4-10 Input/Output Data Setting Information Where Node Address = 10111H Bit strobe input data offset0112H Number of bit strobe input data bytes0113H Polling input data offset0114H Number of polling input data bytes0115H Polling output data offset0116H Number of polling output data bytes