Functions6.24 [3.11] Maintenance & Diagnostics > TestOperating with the Local User InterfaceOperating Manual, 06/2017, A5E31930478-05 237Procedure1. Main menu > "3. Maintenance & diagnostics" > "11. Test" > "1. Test inputs/outputs" >"1. Analog outputs"Use this menu to access the assigned test parameters of all analog outputs. You can alsostart the test function for all activated analog outputs.NoteEquipment-dependent displayOnly the analog outputs actually available on the device are listed in the menu. Example:• Analyzer module 1 with a component exists: Only analog output AO11 is displayed• Analyzer modules 1 and 2 exist each with one component: The analog outputs AO11and AO21 are displayed.NotePrinciple of operationWhen you enable the test function, the analog outputs are released from their actualfunction.The navigation lines of the menus are structured as follows:Structure of the navigation lines1. Test mode Active 1)Edit ►2. AO11: O2 2) 3) 4) 4 mA 5)Specify setpoint for testing ►1) Activity indicator test mode (active/ inactive)2) Designation of the analog output and the component3) AM1: AO11 (component 1), AO12 (component 2), AO13 (not assigned)4) AM2: AO21 (component 3), AO22 (component 4), AO23 (not assigned)5) Actual value display2. Enter setpoint for testing the first analog output, e.g.:Main menu > "3. Maintenance & diagnostics" > "11. Test" > "1. Test inputs/outputs" >"1. Analog outputs" > "2. AO01: ..."3. Specify unit for setpoint to be defined: "Setpoint input" parameter field.– Authorize access with Standard PIN, if necessary.– Depending on the measuring device, select the value "mA" or "Gas unit".4. Specify the test setpoint: "Setpoint in mA" or "Setpoint in gas unit" parameter field.– When you output the setpoint in the gas unit, the analog output is output depending onthe assigned measuring range.– Enter the corresponding value.