H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 71I/O modules Parts of the H-S81-HS System2.4.10 S81-F6002-1DescriptionLogic module able to control 100 S-R flip flops, 100 toggles, and 100 timers.Timers can be configured for two operating modes (Mode-A and Mode-B).Technical FeaturesStatus IndicationsThe front panel includes four LEDs with the following functions:ConfigurationBy using the ProS81 configuration program, the following parameters can be set for each virtualchannel:Logic FunctionsThe following time diagrams describe in detail the operation of the various logic functions of themodule.• Redundancy: Yes• Maximum number of S-R flip flops: 100• Maximum number of logic Toggles: 100• Maximum number of Timers: 100• Timer range: 0-255 seconds• Supply voltage: 22-29VDC• Quiescent current: 9mA• Operating temperature: -5 - 50 °C• Storage temperature: -30 - 80 °C• Maximum humidity: 95% (RH) non-condensing• Hot swap capability: yesLED IndicationF1 (Green LED) Steady on if a logic function input variable is activeF2 (Green LED) Steady on if a logic function output variable is activeF3 (Green LED) Flashing during Timer count.Disabled (Yellow LED) Steady on if an input or output variable is disabledParameter Type ModeType Sensors Flip Flop / Toggle / TimerMode Sensors A / B (Only for Timer types)Alarm delay Sensors 0-255 seconds (Only for Flip Flop and Timer types)Type of indication Sensors Fire, Supervisory, Gas, Trouble, Hidden, Buzzer OnlyEnable/Disable status export to Hosts Sensors/Actuators No, TCP1, TCP2, RS232Enable/Disable commands from Hostson the channelSensors/Actuators No, TCP1, TCP2, RS232NOTE: Logic function virtual inputs are set in output zones, whereas logic function virtualoutputs are set in zone sensors.