H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 101Termination modules Parts of the H-S81-HS SystemField Connections2.5.8 S81-T8007-2DescriptionThis module is used together with moduleS81-F5003-1 and allows to control up to 4 sound-ers with a maximum absorption of 2A each.Technical FeaturesStatus IndicationsThe module includes 4 green LEDs for output status indication:Internal Connections BR1 Terminal Block2-way terminal block for power supply connection.SPDT contactsNC = Normally closedNO = Normally openCOM = CommonK1 K2 K3 K4 K5 K6 K7 K8NCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOM1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24BR1K9 K10 K11 K12 K13 K14 K15 K16NCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOMNCNOCOM1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24BR2! CAUTION: EN-54-2 COMPLIANCETHE OUTPUTS ABOVE ARE NOT C-, E- OR J-TYPE OUTPUTS (EN 54-1), THEREFORE THEYMUST NOT BE USED TO CONTROL FIRE ALARM DEVICES OR ALARM, FIRE ALARM ORFAULT ALARM TRANSMISSION DEVICES. THIS GUARANTEES COMPLIANCE WITHSTANDARD EN-54-2.• Supply voltage: 22-29VDC• Quiescent current: 0mA• Max. output current 2A - current protected• Assembly: on DIN bar• Operating temperature: -5 - 50 °C• Storage temperature: -30 - 80 °C• Maximum humidity: 95% (RH) non-condensing• Dimensions: W 78 x H 77 x D 50 mmLED ConditionLED1 - LED4 (Green LEDs) They light up when outputs are activeTag Function Notes∅ M1 25VDC power supply positive Red∅ M2 25VDC power supply negative Black