H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 55I/O modules Parts of the H-S81-HS SystemEnd of Scale CalibrationCalibrate the end of scale as follows:• Disable the channel of the module to be calibrated from the operator cycle.• Enter the diagnosis cycle of the module to be calibrated.• Apply gas to the sensor according to the percentage set during configuration.• Wait for the gas value measured by the module to stabilize.• Press the key “3” to calibrate the end of scale for channel 1.• Press “2” to cancel the operation for channel 1.• Press the key “7” to calibrate the end of scale for channel 2.• Press “6” to cancel the operation for channel 2.• Exit the module diagnosis cycle and enable the channel.Field ConnectionsThe module can be connected to field terminal block by using a flat or a multi-conductor cable,depending on the used bus type. S81-E2001-1 BusThe module is connected to a S81-T8003-1 termination module with 8 termi-nals with a 20-way flat cable. S81-E2001-2 BusThe module is connected to the field terminal block with the S81-CCT7 16-conductor multi-polar cable. For S81-F4002-2 module redundant connection,use the S81-CCT7R cable.NOTE: The end of scale can be calibrated only if the current value measured by the module is±3mA than the set calibration value.