60 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015Parts of the H-S81-HS System I/O modules2.4.5 S81-F5001-1 & S81-F5001-2Description8 x 500 mA monitored control channel module. This is especially suited to con-trol automatic fire extinguishing systems, and can be used both for controllingdirectional and releasing solenoid valves and evacuation visual and audiblealarm devices. During operation, each channel is cyclically tested by the modulethrough reversal of output signal for approximately 200 hundreds of microsec-onds. In case of difference between the set signal and the measured one, the con-trol panel promptly signals a fault. Several channels can be connected in parallelin order to increase the output current. This module can be duplicated in faulttolerant systems; in this case, the two modules shall be placed on adjacent racksin the same position. In this configuration, the eight output lines are connectedto both modules.Technical FeaturesStatus IndicationsEach one of the eight channels on the front panel includes two status LEDsConfigurationBy using the configuration program ProS81, the following parameters can be set for each outputchannel:• Safety rating: applicable up to SIL3• Redundancy: S81-F5001-2 model• Channel test: every 2 seconds• Max. output current: 500mA• Automatic output protection: Yes• Supply voltage: 22-29VDC• Quiescent current: 35mA• Operating temperature: -5 - 50 °C• Storage temperature: -30 - 80 °C• Maximum humidity: 95% (RH) non-condensing• Hot swap capability: yesOutput Channel Status Indications 1-8 Out LEDsYellow LED RED LEDOff − −Disabled ⊗ −Trouble ∅ −Active − ⊗Key to symbols ⊗= steady on LED; − = LED off; ∅= flashing LEDFunction ModeOperating mode Continuous-Normally Energized, Continuous-Normally de-energized, Intermittent,Pulsing-1, Pulsing-2, ISA-1A Alarm Sequence, Delayed on activation, Delayed onenabling, Delayed on deactivationTiming 1 to 255 seconds/minutes (only for pulsing and intermittent modes)Output type Normal / SounderOutput status in case of CPU fault Frozen in the last status / OffEnable/Disable status export to Hosts No, TCP1, TCP2, RS232Enable/Disable commands from Hostson the channelNo, TCP1, TCP2, RS232