18 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015General Description General Features1.3.2 Electrical Characteristics1.3.3 Reference StandardsThe H-S81-HS system was developed complying with the requirements of the following Europeanstandards:1.3.4 Climatic ConditionsThe table below summarizes the climatic conditions for H-S81-HS system operation and storage.The climatic conditions refer to the whole system.1.3.5 Mechanical ConditionsThe table below summarizes the type of mechanical tests undergone by the H-S81-HS system.• Supply voltage 110-240 V~ (-15% + 10%)• Nominal frequency of the power supply 50-60Hz• Power supply set output voltage 25VDC ±2%Reference standard DescriptionEN-54-2:1997 / A1:2006 Fire detection and fire alarm systemsPart 2: Control and indicating equipmentEN-54-4: 1997 / A1:2002 / A2:2006 Fire detection and fire alarm systemsPart 4: Power supply equipmentEN-12094-1:2003 Fixed firefighting systems. Components for gas extinguishing systems.Requirements and test methods for electrical automatic control and delay devicesEN-60950-1:2001 Information technology equipment – Safety - part 1:General requirementsCEI 79-2:1998 + Ab2000 Intruder, burglar, hold up and anti-attack alarm systems. Particular requirementsfor apparatus.Parameter Allowed range NotesOperating temperature -5 - 50°CStorage temperature -40 - 85°COperating humidity 5 - 95% RH Non-condensingStorage humidity 5 - 95% RH Non-condensingNOTE: The operating temperature inside an electronic device significantly affects the duration ofits useful life. High operating temperatures and sharp temperature increases will significantlyreduce electronic device life. It is extremely important that the environmental operating conditionsare within the allowed ranges.! WARNING: REMOVE BATTERIESSHOULD STORAGE TEMPERATURE BE LOWER THAN -30°C OR EXCEED +60°C, REMOVETHE LITHIUM BATTERY ON CENTRAL UNITS (S81-U1002-1 MODULES).Standard Test Test LevelsIEC 68-2-6 Vibration sinusoidal test (endurance) Frequency range: 10-150HzAcceleration amplitude: 0.5gNumber of axis: 3Number of sweep cycles: 20 per axisIEC 817 Impact test Impact energy: 0.5JNumber of impact per point: 3