ADAM-4000 Series User Manual 74Figure 3.64 ADAM-4056SO 12-channel Source Type Isolated Digital OutputModule3.18.1 Technical Specification of ADAM-4056SO– Number of Output Channel: 12– Digital Output: VCC: +10 ~ 35VDC, 1A per Channel ( Source)– LED Indicator: On: Active, Off: Non-active– Power Consumption: 1 W @ 24VDC– Optical isolation: 5000 VDC– Supports Modbus/RTU protocol– I/O Connector Type: 10 pin plug-in terminal*2– Leakage current : 50μA– Support Safety Value:Force the DO channels to safety status when communication is in time-outand over pre-defined period.