ADAM-4000 Series User Manual 122Table 5.2: ADAM-4015/4015T command codes against Input rangestableCommand Code (Hex) Input Type Input Range20 Platinum 100 (IEC) -50 ~ 150 °C21 Platinum 100 (IEC) 0 ~ 100 °C22 Platinum 100 (IEC) 0 ~ 200 °C23 Platinum 100 (IEC) 0 ~ 400 °C24 Platinum 100 (IEC) -200 ~ 200 °C25 Platinum 100 (JIS) -50 ~ 150 °C26 Platinum 100 (JIS) 0 ~ 100 °C27 Platinum 100 (JIS) 0 ~ 200 °C28 Platinum 100 (JIS) 0 ~ 400 °C29 Platinum 100 (JIS) -200 ~ 200 °C2A Platinum 1000 -40 ~ 160 °C2B BALCO 500 -30 ~ 120 °C2C Ni 604 -80 ~ 100 °C2D Ni 604 0 ~ 100 °C30 Thermistor 3K 0 ~ 100 °C31 Thermistor 10K 0 ~ 100 °C33 Ni 508 -50 ~ 200 °CIEC RTD 100O, α = 0.00385JIS RTD 100O, α = 0.00391Input Range Code (Hex) Input Range for 4019+02 ± 100 mV03 ± 500 mV04 ± 1 V05 ± 2.5 V07 +4~20mA08 ± 10 V09 ± 5 V0D ± 20 mA0E Type J Thermocouple 0 ~ 760 °C0F Type K Thermocouple 0 ~1370 °C10 Type T Thermocouple -100 ~ 400 °C11 Type E Thermocouple 0 ~ 1000 °C12 Type R Thermocouple 500 ~ 1750 °C13 Type S Thermocouple 500 ~ 1750 °C14 Type B Thermocouple 500 ~ 1800 °C