ADAM-4000 Series User Manual 1404015, 4015T, 4017+, 4018+, 4019+5.1.18 $AA7CiRrrName Single Channel Range Configuration commandDescription This command configures the input type and range of thespecified channel in an analog input module.Syntax $AA7CiRrr(cr)$ is a delimiter character.AA (range 00-FF) represents the 2-character hexadecimaladdress of the analog input module which is to be configured.7 is the Single Channel Range Configuration command.Ci represents the specified input channel you want to configure.Rrr represents the type and range you want to set. (Refer toTable 5.1 on Page 5-6 to check range codes)(cr) is the terminating character, carriage return (0Dh).Response !AA(cr) if the command was valid.?AA(cr) if an invalid operation was entered.There is no response if the module detects a syntax error orcommunication error or if the specified address does not exist.! delimiter character indicates a valid command was received.? delimiter character indicates the command was invalid.AA (range 00-FF) represents the 2-character hexadecimaladdress of the analog input module.(cr) represents terminating character, carriage return (0Dh).Example command: $027C5R21(cr)response: !02(cr)The command configures the range of channel 5 in theanalog input module at address 02 as Pt100(IEC) 0 ~ 100 °C