99 ADAM-4000 Series User ManualChapter 4 Command SetTable 4.12: ADAM-4018+ Input range and external calibrating inputsource for each input typeRangebcode(Hex) Input Range Max. Signal Min Signal DisplayedResolution06 +/-20 mA +20.000 -20.000 1uA07 4~20 mA +20.000 +4.000 1uA14 Type JThermocouple15 Type KThermocouple16 Type TThermocouple17 Type EThermocouple18 Type RThermocouple19 Type SThermocouple20 Type BThermocoupleTable 4.13: ADAM-4018M Command TableCommand Syntax Command Name Command Description Page No.%AANNTTCCFF ConfigurationSets the address, input range, baudrate, data format, checksum status,and/or integration time for a specifiedanalog input module5-4$AA2 Configuration Status Return the configuration parametersfor the specified analog input module 5-10$AAF Read VersionReturn the firmware version codefrom the specified analog input mod-ule5-12$AAM Read Module Name Return the module name from thespecified analog input module 5-13#AAN Read Analog Inputfrom Channel NReturn the input value from channelsnumber N of the specified analoginput module5-16$AA5VVEnable/DisableChannels for Multi-plexingEnable or disable the individual chan-nels in an analog module 5-17$AA6 Read Channel Status Get the enable/disable status of allchannels in an analog module 5-18$AA0 Span Calibration Calibrates an analog input module tocorrect for gain errors 5-19$AA1 Offset Calibration Calibrates an analog input module tocorrect for offset errors 5-20$AA3 CJC Status Returns the value of the CJC sensorfor a specified analog input module 5-25$AA9SNNNN CJC OffsetCalibrationCalibrates the CJC sensor for offseterrors 5-26