ADAM-4000 Series User Manual 1504018M5.2.5 @AATName Read Memory Operation Mode commandDescription Request the memory operation status of the analog inputdata logger at address AA.Syntax @AAT (cr)@ is a delimiter character.AA (range 00-FF) represents the 2-character hexadecimaladdress of an analog input data logger.T is the Read Memory Operation Mode command.(cr) is the terminating character, carriage return (0Dh).Response !AAO(cr) if the command is valid.! is a delimiter character indicating a valid command was received.AA (range 00-FF) represents the 2-character hexadecimaladdress of an analog input module.O represents the operation mode:‘1’: enables the recording of data.‘0’: disables the recording of data.(cr) is the terminating character, carriage return (0Dh).Example command: @F3T(cr)response: !F31(cr)The command requests the memory operation status of theanalog input data logger at address F3.The response indicates that data recording is enabled.